Type of facility
|
indirect cooling system
|
Refrigerant
|
NH3
|
Refrigerant volume
|
160 kg
|
Secondary refrigerant
|
ethylene glycol / water
|
Refrigeration
|
2 liquid chillers with 2 ammonia-screw compressors each, Model SAB 128 HF, at -16/40 °C refrigerating capacity 220 kW,
2,960 RPM
1 brine cooler plate heat exchanger 405 kW
1 condenser plate heat exchanger 550 kW
|
1 common evaporative cooler
|
for both units (closed system recirculating glycol / water) 1,100 kW
|
Cold glycol cycle
|
for 30 x 60 m rink with 21 km of rink piping in DN 20, recirculation volume 280 m³/h
|
Warm glycol cycle
|
for condensing and underfloor heater to prevent substrate freezing, recirculation volume
220 m³/h
|
Cooling consumers
|
1 defrosting system for the rink sole with heat exchanger 1,000 kW
|
1 water treatment unit
|
for the indirect condenser cooler and for icing the rink*
|
Surface area of the ice
|
1,800 m²
|
Stadium capacity
|
13,000
|
Special features / Comments
|
* top-quality ice through fully desalinated water
|